Active power transducers |
Powertek UK Tel: +44 1788 519911 US Tel: +1 631 615 6279 Email : info@powertekus.com Email : info@powertekuk.com |
Return to Homepage | contact us | Offices
Selection Guide |
MT100-WA1 | Single Phase |
MT100-WA2 | 3 phase 3 wire balanced load |
MT100-WA3 | 3 phase 4 wire balanced load |
MT100-WA4 | 3 phase 3 wire unbalanced |
MT100-WA5 | 3 phase 4 wire unbalanced load |
MT100-WA6 | 3 phase 3 wire balanced load externally connected |
reverse CT'S | |
MT100-WA7 | 3 phase 3 wire balanced load, internally reversed CTs, 1 x V input & 2 x A inputs |
Typical Applications |
The MT100-WAx series measures active power in single, 3 phase 3 or 4 wire balanced and unbalanced systems. Using the time division multiplier circuit means that they can be used over a wide range of input waveshapes. The D.C. Output signal is directly proportional to the instantaneous real power. Typical applications include the measurement of power in switchboards, power stations, generating sets. |
Technical Specifications |
INPUT | |
Rated value In | 1A or 5A C.T. connected or 0.5A-10A direct |
connected | |
Rated value Un | 57.8Vrms to 600Vrms |
Power Consumption | <1VA voltage <0.2VA current |
Working Range | 0-125% Un auxiliary powered and 75%-125% Un / |
0-150% In when self powered | |
Rated Frequency | 50/60/400Hz |
Frequency Influence | 0.005% Hz |
Overload Continuous | 4 x In 1.5 x Un |
Overload for 1 sec | 50 x In 2 x Un |
OUTPUT | |
Rated value mA | 0-1/5/10/20 & 4-20mA |
Rated value volts | 0-5, 0-10 & 1-5V |
ADJUSTMENT | |
Zero | ±2% |
Span | ±10% |
AUXILIARY | |
A.C. Voltage | 115/230/400V (±25%/45-65Hz/<2VA) |
D.C. Voltage | 24/48/110V (±20%/galvanically isolated/<3W) |
WEIGHT & CASE SIZE | |
MT100-WA1,2,3,6,7 | Approx 0.6kg. 100mm case |
MT100-WA4,5 | Approx 0.8kg. 100mm case |
Ordering Information |
Product Code | Un | O/P | Range | Aux | Freq | Opt |
MT100-WA5 | 230V | 0-20mA | 600kW | 230V | 50Hz |
Options |
1 | Non standard Inputs/Outputs as far as technically viable |
2 | A.C. Auxiliary in range 57.7 to 450 volts |
3 | Calibration at nominal Hz 35....450Hz |
4 | Calibration at temperature other than 23șC |