Reactive power VAr transducers

Powertek
 UK Tel: +44 1788 519911
 US Tel: +1 631 615 6279
 Email : info@powertekus.com
 Email : info@powertekuk.com


Return to Homepage | contact us | Offices

Selection Guide

MT100-XA1 Single Phase
MT100-XA2 3 phase 3 wire balanced load
MT100-XA3 3 phase 4 wire balanced load
MT100-XA4 3 phase 3 wire unbalanced load
MT100-XA5 3 phase 4 wire unbalanced load
MT100-XA6 3 phase 3 wire balanced load externally connected
  reverse C.T's
MT100-XA7 3 phase 3 wire balanced load internally reversed C.T's

Typical Applications

The MT100-XA series measure reactive power in single, 3 phase 3 or 4 wire balanced and unbalanced systems. Using the time division multiplier circuit means that they can be used over a wide range of input waveforms. The D.C. output signal is directly proportional to the  instantaneous reactive power being measured. Typical Applications include the measurement of reactive power in switchboards, power stations and generating sets etc. The high isolation of 4kV as with all MT100 series allows these VAr transducers to be connected to a variety of measuring and control devices and systems, such as  analogue meters, PLC, computer systems, data loggers, digital instruments and telemetry systems. Both auxiliary powered and self powered versions of each  type are available. It is recommended to use an auxiliary powered version if the system being measured has voltage variations in excess of ±20%

Technical Specifications

INPUT  
Rated value In: 1A or 5A C.T connected or 0.5A-10A direct connected
Rated value Un: 57.8Vrms to 600Vrms
Power Consumption < 1VA voltage < 0.2VA current
Working Range 0-125% Un auxiliary powered or 75%-125% Un self
  powered 0-150% In
Rated Frequency 50 / 60 / 400Hz
Frequency Influence 0.005% / Hz
Overload continuous 4 x In 1.5 x Un
Overload for 1 sec. 50 x In 2 x Un
OUTPUT  
Rated value mA 0-1/5/10/20mA & live zero 4-20mA
Rated value volts 0-5V/0-10V & live zero 1-5V
ADJUSTMENT  
Zero ±2%
Span ±10%
AUXILIARY  
A.C. Voltage 115 / 230 / 400V (±25%/45-65Hz/<2VA)
D.C. Voltage 24/48/110V (±20%/galvanically isolated/<3W)
WEIGHT&CASE SIZE  
MT100-XA1,2,3,6,7 Approx 0.6kg. 100mm case
MT100-XA4,5 Approx 0.8kg. 100mm case

Ordering Information

Product Code IP In Un O/P Range Aux Freq Opt
MT100-XA4 400/5A 400 0-20mA 300kW 120v 50Hz  

Options

1 Non standard inputs / outputs as far as technically viable
2 A.C. Auxiliary in range 57.7 to 450 volts
3 Calibration at nominal Hz 35....450Hz
4 Calibration at temperature other than 23șC

Connection Diagrams

 

trans_icon Main Transducer Page                         Return to Powertek Homepage